ABB Drives - ACS380-040C 240V Drives with Options

SKU
ACS380-040C-12A2-2+K492
Contact For Lead Time
ACS380, Light Duty (110% overload) HP: 3 HP, Light Duty (110% overload) Output Current: 11.6 A, Heavy Duty (150% overload) HP: 3 HP, Heavy Duty (150% overload) Output Current: 9.8 A, Voltage: 240 VAC, Input Voltage Range: 200-240V, UL Type Open (IP20), Cabinet-mounted, Integral and/or remote mount control panel with keypad and LCD display, 1-Phase OR 3-Phase Input, 3-Phase Output, Frame: R2, Product Dimensions HxWxD (in): 8.8 x 3.7 x 6.9, Product Weight (lb): 4.2. Options included: PROFINET IO Two Port Adapter,
$1,129.65
Number of Phases3
Degree of ProtectionIP20
Enclosure Type NEMAOpen Type
Operating Humidity (RHamb)5 ... 95
Power Factor0.98
Multiple Battery InformationNo battery / cell included
Frequency (f)47.5 ... 63 Hz
Input Voltage (Uin)200 ... 240 V
Mounting TypeModule for cabinet building
Communication ProtocolCAN
DeviceNet
EtherNet/IP
MODBUS
Other Bus Systems
PROFIsafe
PROFIBUS
PROFINET IO
TCP/IP
Number of Hardware InterfacesIndustrial Ethernet 0
Other 3
Parallel 0
PROFINET 0
RS-232 0
RS-422 0
RS-485 0
Serial TTY 0
USB 0
IncludesControl unit
PC connection
Analog Inputs0
Analog Outputs0
Number of Digital In/Outputs2 / 1
Output Current, Heavy-Duty Use (IHD)9.8 A
Output Current, Light-Overload Use (ILD)11.6 A
Output Current, Normal Use (In)12.2 A
Output Power, Heavy-Duty Use (PHD)2.2 kW
Output Power, Light-Overload Use (PLD)3.0 kW
Output Power, Normal Use (Pn)3.0 kW
Apparent Power Output4.9 kV·A
Efficiency LevelIE2
Standby Loss15 W
Complete Drive Module Efficiency (61800-9-2)
Operating Point
Frequency / Current
Absolute
Loss
EfficiencyRelative
Loss
0/25 %65 W79.8 %1.3 %
0/50 %79 W86.3 %1.6 %
0/100 %114 W89.0 %2.3 %
50/25 %69 W88.6 %1.4 %
50/50 %86 W92.3 %1.8 %
50/100 %129 W93.7 %2.6 %
90/50 %96 W95.1 %2.0 %
90/100 %149 W95.9 %3.1 %
Temperature RatingMaximum 50 °C
Output Current, Heavy-Duty Use (UL)9.3 A
Output Current, Light-Overload Use (UL)11.6 A
Output Power, Heavy-Duty Use (UL)3 Hp
Output Power, Light-Overload Use (UL)3 Hp